16751563672348
16751563709644
16751563713615
16751563672348
16751563709644
16751563713615

High Voltage 3Phase Hybrid Inverter GSL-10/ 12/ 15KHV-3PH

An on-grid inverter’s main job is to convert DC power generated from the PV array into usable AC power. Hybrid inverters go a step further and work with batteries to store excess power as well. In the developing world, hybrid inverters are more of a necessity to compensate for weak or intermittent grids or a lack of grid electricity all together.

ModelGSL-10KHV-3PHGSL-15KHV-3PHGSL-20KHV-3PH
Battery Input Data
Battery TypeLi-Ion
Battery Voltage Range (V)160~700
Max.Charging Current (A)37
Max.Discharging Current (A)37
Number of Battery Input1
Charging Strategy for Li-on BatterySelf-adaption to BMS
PV String Input Data
Max.DC Input Power (W)130001950026000
Max.DC Input Voltage (V)1000
Start-up voltage (V)180
MPPT Range (V)150-800
Full Load DC Voltage Range (V)325-850420-850500-850
Rated DC Input Voltage (V)600
PV Input Current (A)20+2026+2026+26
Max. PV I SC (A)30+3039+3039+39
No.of MPPT Trackers2
No.of Strings Per MPPT Trackers12+12
AC Output Data
Rated AC Output and UPS Power (W)100001500020000
Max. AC Output Power (W)110001650022000
AC Output Rated Current (A)15.2/14.522.8/21.830.4/29
Max. AC Output Rated Current (A)16.7/1625/2433.4/31.9
Max. Three-phase Unbalanced Output Current (A)223035
Max. Continuous AC Passthrough (A)4080
Peak Power (off grid)1.5 time of rated power, 10 S
Generator input/Smart load /AC couple current (A)15.2/40/15.222.8/80/22.830.4/80/30.4
Power Factor0.8 leading to 0.8 lagging
Output Frequency and Voltage50/60Hz; 3L/N/PE 220/380, 230/400Vac
Grid TypeThree Phase
DC injection current (mA)<0.5%1n
Efficiency
Max. Efficiency97.60%
Euro Efficiency97.00%
MPPT Efficiency99.90%
Protection
IntegratedPV Input Lightning Protection, Anti-islanding Protection, PV String Input Reverse Polarity Protection, Insulation Resistor Detection, Residual Current Monitoring Unit, Output Over Current Protection, Output Shorted Protection, Surge protection
Output Over Voltage ProtectionDC Type II/AC Type III
Certifications and Standards
Grid RegulationVDE4105, IEC61727/62116, VDE0126, AS4777.2, CEI 0 21, EN50549-1, G98, G99, C10-11, UNE217002,  NBR16149/NBR16150
Safety EMC / StandardIEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2
General Data
Operating Temperature Range(℃)-25~60℃,>45℃ Derating
CoolingSmart cooling
Noise (dB) <45
Communication with BMSRS485;CAN
Weight (kg)30.5
Size (W*H*D)408×638×237mm
DegreeIP65
Installation StyleWall-mounted
Warranty5 years